Seite 1 - Administrator's Guide

53-1003144-0127 June 2014FICONAdministrator's GuideSupporting Fabric OS v7.3.0

Seite 2

• OEM/Solution Providers are trained and certified by Brocade to support Brocade® products.• Brocade provides backline support for issues that cannot

Seite 3 - Contents

• Verify the FICON CUP license is installed.• Check the state of the CUP by running the ficonCupShow fmsmode command. If it is disabled,enter the fico

Seite 4

Platforms Supporting FICON● Introduction...

Seite 5

Supported platforms with end-of-support announcements (Continued)TABLE 10 Brocade4900Fabric OSBrocade5000Fabric OSBrocade6140Fabric OSBrocadei10KFab

Seite 6

Currently supported platforms (Continued)TABLE 11 Brocade7800, 7840Fabric OSBrocade5300Fabric OSBrocadeDCX-4SFabric OSBrocadeDCXFabric OSBrocadeDCX

Seite 7 - Document conventions

Unsupported bladesThe following port blades are not supported in a FICON environment:• FCOE10-24• FS8-18• FC4-48• FC8-32E• FC8-48EUnsupported blades10

Seite 8 - Notes, cautions, and warnings

Basic Switch ConfigurationThis appendix provides basic steps and commands to quickly configure a switch for fabric and possibleFICON and cascaded FICO

Seite 9 - Brocade resources

Switch configuration example and commands (Continued)TABLE 13 Feature Relevant CommandsRepeat the following procedure to configure switch parameters

Seite 10 - Document feedback

Switch configuration example and commands (Continued)TABLE 13 Feature Relevant CommandsIf you are enabling FMS (CUP), disable all ports assigned add

Seite 11 - About This Document

Switch configuration example and commands (Continued)TABLE 13 Feature Relevant CommandsSet port fencing. Setting port fencing parameters is much eas

Seite 12

Address Binding Examples● Sequential address binding...107● Po

Seite 13 - Introducing FICON

About This Document● Supported hardware and software... 9● Additional

Seite 14 - Latency guideline

Example scripts for binding portsThe following example scripts containing the portAddress --bind command bind all ports on the DCXBackbone to sequenti

Seite 15 - FICON concepts

# Slot 3portaddress --bind 3/0 4000portaddress --bind 3/1 4100portaddress --bind 3/2 4200portaddress --bind 3/3 4300portaddress --bind 3/4 4400portadd

Seite 16 - FICON configurations

portaddress --bind 9/11 8B00portaddress --bind 9/12 8C00portaddress --bind 9/13 8D00portaddress --bind 9/14 8E00portaddress --bind 9/15 8F00portaddres

Seite 17 - Cascaded FICON

portaddress --bind 11/23 D700portaddress --bind 11/24 D800portaddress --bind 11/25 D900portaddress --bind 11/26 DA00portaddress --bind 11/27 DB00porta

Seite 18

Port-based address bindingThis section provides an example that will allow all ports on all blades installed in a Brocade DCXBackbone to use port-base

Seite 19

portaddress --bind 1/11 0B00portaddress --bind 1/12 0C00portaddress --bind 1/13 0D00portaddress --bind 1/14 0E00portaddress --bind 1/15 0F00portaddres

Seite 20

portaddress --bind 3/23 A700portaddress --bind 3/24 A800portaddress --bind 3/25 A900portaddress --bind 3/26 AA00portaddress --bind 3/27 AB00portaddres

Seite 21

portaddress --bind 10/2 5200portaddress --bind 10/3 5300portaddress --bind 10/4 5400portaddress --bind 10/5 5500portaddress --bind 10/6 5600portaddres

Seite 22

portaddress --bind 12/14 7E00portaddress --bind 12/15 7F00portaddress --bind 12/16 F000portaddress --bind 12/17 F100portaddress --bind 12/18 F200porta

Seite 23

Configuration Information RecordYou can use the following worksheet for recording FICON configuration information.NOTEAttached E_Ports can be for an I

Seite 24

• Added notes wherever configupload command mentioned that it backs up Fabric OS feature andswitch configuration, but not FMS and FICON-specific confi

Seite 25 - Access control in FICON

Configuration Information Record118 FICON Administrator's Guide53-1003144-01

Seite 26 - Cascaded zoning

EBCDIC Code PageExtended Binary Coded Decimal Interchange Code (EBCDIC) is an 8-bit character encoding (codepage) used on IBM mainframe operating syst

Seite 27

EBCDIC Code Page120 FICON Administrator's Guide53-1003144-01

Seite 28 - Secure access control

Index256-area addressing mode 44Aaddressinglink and FC 30modes 44address modechanging 45FICON and blade support 46automating CS_CTL mapping 47Bbest pr

Seite 29

FICON supportblades 101blades not supported 102platforms 100firmware management 77firmware upload and download 78FMS modedisabling 58displaying 58enab

Seite 30 - FICON commands

SSCC policycreating and activating 34deleting 36security policy, create 41security-related commands 36session-based zoning enforcement 23, 79single-sw

Seite 31

124 FICON Administrator's Guide53-1003144-01

Seite 32 - Link and FC addressing

Introducing FICON● FICON overview...11● FIC

Seite 33 - Port area

Disables the dynamic domain ID feature and only allows the switch to use a pre-set domain ID. Allswitches in a fabric must have a unique domain ID. An

Seite 34

FICON conceptsThe following figure shows how the traffic in a switched point-to-point configuration flows in a FICONenvironment. The logical path of t

Seite 35 - Administering FICON Fabrics

A unit of FICON data consisting of from one to four Fibre Channel frames.• Link Incident Record Registration (LIRR)The LIRR Extended Link Service (ELS

Seite 36

Switched point-to-pointA single-switch configuration is called switched point-to-point allows the channel to use single-byteaddressing.FIGURE 2 Switch

Seite 37

switches and backbones is also supported. An example of this would be a Brocade DCX 8510-8Backbone connected to a Brocade 6510.A cascaded configuratio

Seite 38 - Preparing a switch for FICON

resulting fabric scenario after ISL failures must not result in an unsupported configuration. Whenphysical cabling is not practical to enforce these c

Seite 39

© 2014, Brocade Communications Systems, Inc. All Rights Reserved.Brocade, the B-wing symbol, Brocade Assurance, ADX, AnyIO, DCX, Fabric OS, FastIron,

Seite 40

The following figure illustrates a multi-hop ICL triangle configuration that uses ICLs. Note that threeswitches are connected through ICLs only.FIGURE

Seite 41

The following figure illustrates a multi-hop configuration that uses ICLs and ISLs. This configuration issupported with or without switches 4 or 1. Al

Seite 42

supported with or without switches 4 or 1. All switches must be Gen 4 or Gen 5. You cannot mix Gen 4and Gen 5 switches with ICLs.FIGURE 8 Multi-hop wi

Seite 43 - Configuring cascaded FICON

The following figure illustrates a configuration that uses FCIP between 7800 switches that are used asrouters only, for ISL extension. Channel or cont

Seite 44 - FCR and FICON cascading

permitted. The 7800 switches at site 2 are only for network, channel, and control unit connections. The7800 switches on either site may be replaced wi

Seite 45

the 7800 switches. The 7800 switches at either site may be replaced with the FX8-24 blades installed indirectors.FIGURE 11 Cascaded configuration usin

Seite 46 - Addressing modes

devices to changes in the fabric. Using multiple smaller zones instead of one large zone helpsalleviate the need for channels and device interfaces to

Seite 47 - Changing the addressing mode

NOTEZoning does not replace the need to set up the connectivity from the host to storage control units in theHCD or Input/Output Configuration Program

Seite 48 - Port swap limitations

Error reportingNon-implicit link incidents (such as Fabric OS recognized or bit error rate threshold exceeded) andimplicit link incidents (such as FRU

Seite 49 - Automating CS_CTL mapping

The figure below demonstrates the three types of binding you can use depending on the securityrequirements of your fabric.FIGURE 14 Types of binding f

Seite 50

ContentsPreface...5D

Seite 51 - FICON best practices

FICON commandsNOTEThe Fabric OS CLI supports only a subset of the Brocade management features for FICON fabrics.The full set of FICON CUP administrati

Seite 52

Fabric OS commands related to FICON (Continued)TABLE 1 Command DescriptionportSwap Swaps ports. Note that the portswap --restorecommand restores swa

Seite 53 - Configuring FICON CUP

Fabric OS commands related to FICON (Continued)TABLE 1 Command DescriptionficonCupShow diag_infoDisplays the diagnostic interval setting and related

Seite 54 - FICON CUP restrictions

The following figure represents components of link and FC addresses that are explained in this section.FIGURE 15 Link and FC address componentsDomain

Seite 55

ALPA32 FICON Administrator's Guide53-1003144-01

Seite 56 - FICON CUP Fabric OS commands

Administering FICON Fabrics● User security considerations... 3

Seite 57

NOTEYou enable the fabric-wide consistency policy on the fabric once the switch joins the fabric.NOTEIf FMS mode is enabled before upgrading to v7.3.0

Seite 58 - FMS mode and FICON CUP

• Enter the secpolicycreate command to add all switches in the fabric, if they are connected.secpolicycreate "SCC_POLICY","*"• Ent

Seite 59

Using other security commandsThe following commands are some other security-related commands that you might find useful.Disabling the fabric-wide cons

Seite 60 - Resetting FMS mode

Cascaded FICON and two-byte addressing considerationsThe following are considerations when installing a switch in a FICON environment where two-bytead

Seite 61 - Upgrade considerations

Mode 0 (10-bit addressing)... 44Mode 1 (zero-based addressing)...

Seite 62 - Mode register bit settings

NOTEIf Lossless DLS is not enabled, the routing policy must be port-based routing (aptPolicy 1).6. Set In-Order Delivery using the iodSet command.7. C

Seite 63 - FICON file access facility

FICON switch parameters (Continued)TABLE 2 Parameter Response CommentSuppress Class Ftraffic0 Do not change. By default, the switch can send Class F

Seite 64

FICON switch parameters (Continued)TABLE 2 Parameter Response CommentRSCNtransmission modeNo Configures end-device RSCN Transmission Mode values suc

Seite 65 - Setting the MIHPTO value

13. Configure the fill word for all 8 Gbps ports using the portCfgFillWord command. The followingexample shows the command with recommended mode 3 and

Seite 66

CAUTIONConfiguring the switch for FICON is a disruptive process. The switch must be disabled toconfigure switch parameters. This procedure must be fol

Seite 67 - FICON emulation overview

3. Add the front domain WWN to the SCC Policy lists in the edge switches to be merged.4. Connect the switches.FICON and FICON CUP in Virtual FabricsFo

Seite 68

An extended interswitch link (XISL) is an interswitch link (ISL) that connects the logical switch to abase switch and carries traffic for multiple log

Seite 69 - Tape emulation

• The default switch is being used for FICON and no 48 or 64 port blades are installed in the chassis.The default switch address mode 0 will be 8-bit

Seite 70 - Tape Read Pipelining

NOTETo access all parameters controlled by the configure command, you must disable the switch. Anyconfiguration change to a logical switch that requir

Seite 71 - Printer emulation

The following tables compare the achievement of port persistent enable and disable states withinteractions between the ASM Mode setting, IPL state. an

Seite 72 - Teradata emulation

Options for displaying statistics...75Maintaining and Troubleshooting FICON...

Seite 73 - FCIP tunnel between sites

frame header. High, medium, and low priority frames are allocated to different virtual channels (VCs).High priority frames receive more VCs than mediu

Seite 74 - Configuring FICON emulation

NOTEThe configureChassis command does not provide options to enable the CS_CTL QoS mode onindividual ports in the chassis. Once you set the mode on th

Seite 75 - Modifying FICON emulation

‐ C3 Discard Frames - 2 per minute‐ Invalid Words - 25 per minute‐ Invalid CRCs - 3 per minute‐ Link Reset - 2 per minute‐ Protocol Error - 2 per minu

Seite 76 - FICON emulation monitoring

Configuring FICON CUP● Control Unit Port overview... 51● Po

Seite 77

FICON Management Server mode (FMS mode) must be enabled on the switch to enable CUPmanagement features. For more information, refer to FMS mode and FI

Seite 78

ATTENTIONOnce FMS mode is enabled, you cannot bind addresses 0xFE or 0xFF to any ports using either theportAddress or wwnAddress commands.• The switch

Seite 79 - Firmware download disruption

FICON CUP zoning and PDCM considerationsThe FICON PDCMs control whether or not communication between a pair of ports in the switch isprohibited or all

Seite 80

Configuring FICON CUPTo set up FICON CUP, use the following procedure.1. Connect to the switch and log in using an account assigned to the admin role.

Seite 81 - Traffic Isolation Zoning

On a Brocade DCX and DCX-4S Backbones, when Virtual Fabrics is not enabled or addressing Mode1 is not used, you must disable physical ports associated

Seite 82 - Enhanced TI Zoning

• Access to switch configuration parameters is serialized.• The active CUP configuration data, including the following, is initialized according to th

Seite 83 - Triangular topology

EBCDIC Code Page... 119Index...

Seite 84

Displaying FMS modeUse the ficonCupShow fmsmode command to display the enabled or disabled state of FMS modefor the switch.Enabling FMS modeBefore ena

Seite 85 - System Data Mover topology

• You must manually disable ports associated with 0xFE and 0xFF using the portDisable commandbefore you can enable FMS mode, but only if there is an a

Seite 86

FICON CUP license. The Mode Register is accessible via Web Tools and the Fabric OScommands.‐ In-band Management is enabled, provided you do not disabl

Seite 87 - Emulation topology

FICON CUP mode register bits (Continued)TABLE 7 DCAMSwitch clock alert mode. When this bit is set on, a warning is issued when the date, tsClockServ

Seite 88

The IPL is not replaced because Active=Saved mode is enabled. A warning message is displayed inthe event log to warn users that the IPL will not be ov

Seite 89 - Port fencing

* *------------------------------------------------------------------ Consider

Seite 90 - FICON information

Persistently enabling and disabling ports for CUPWhen FMS mode is enabled, you cannot use the portCfgPersistentEnable andportCfgPersistentDisable comm

Seite 91 - FRU error reporting

Administering FICON Extension Services● Platforms supporting FICON extension over IP... 65●

Seite 92 - FRU numbers

‐ Capacity 1‐ Consumed 1‐ Configured Blade Slots 1This is a slot-based license for extension switches and blades.• Advanced Extension (FTR_AE)Required

Seite 93 - Blade swapping

primary volume to be located at a distance from its mirrored secondary without encounteringperformance degradation associated with IU pacing.FIGURE 17

Seite 94 - Common FICON issues

Preface● Document conventions...5● Brocade resource

Seite 95

Tape Write PipeliningFICON Tape Write Pipelining improves performance for a variety of applications when writing to tapeover extended distances. FICON

Seite 96

pipeline and requests more data from the tape. If an exception status is received from the device, thereading of data and emulation is terminated.FIGU

Seite 97 - Troubleshooting FICON

• Optimized performance for FICON printers over distance when printers are extended through anFCIP tunnel with FICON emulation.• Intermediate ending s

Seite 98

• FICON networks with FCIP emulating and non-emulating tunnels do not support Dynamic PathSelection (aptpolicy 3) configurations.• When running FICON

Seite 99 - Troubleshooting FICON CUP

Configuring FICON emulationBefore you configure FICON emulation, you need to understand the available options, and whetherthose options are to be impl

Seite 100 - Troubleshooting NPIV

• To create a empty tunnel as a FICON FCIP tunnel, use the following command:portcfg fciptunnel 1/17 create -F -c 1• To modify a tunnel to be FICON en

Seite 101 - Platforms Supporting FICON

FICON emulation monitoringUse the -emul option for the portShow xtun command to display FICON emulation statistics. Thesyntax for this command is port

Seite 102 - Currently supported platforms

|0x041011C500|116301640106040A|H| 0x00| N/A|0000|0000| 34516| 0| 0| 262878|32760||0x04100A9700|116301640106040B|H| 0x3C|0x12|006C|00

Seite 103 - Supported Brocade blades

FICON emulation statistics commands (Continued)TABLE 8 Command Output displayportshow xtun ve_port -ficon -tapeperfFICON tape pipelining performance

Seite 104 - Unsupported blades

Maintaining and Troubleshooting FICON● Firmware management in a FICON environment... 77● Confi

Seite 105 - Basic Switch Configuration

Convention Descriptionvalue In Fibre Channel products, a fixed value provided as input to a commandoption is printed in plain text, for example, --sho

Seite 106

• During the firmware download process, a failover to the backup processor occurs. Anyoutstanding CUP commands are lost which results in a timeout. To

Seite 107

Backup and restore in a FICON CUP environment TABLE 9 ASM bit Command Descriptionon or offconfigUploadAll the files saved in the fileaccess facility

Seite 108

Fabric OS v6.2.0 or later is required for TI Zoning in a FICON fabric. For more information on TIZoning, refer to the Fabric OS Administrator's G

Seite 109 - Address Binding Examples

Triangular topologyThe triangular topology shown in the figure below is a common FICON deployment for managing datacenter recovery functions. In this

Seite 110

The figure below shows that the setup allows a source device to reach two separate destinations overexclusive, one-hop paths, while preventing the sou

Seite 111

System Data Mover topologyThe figure below shows a cascaded topology which can be used to support an operations recovery site.In this environment, hos

Seite 112

goes down. Supporting these two functions requires the ability to define overlapping zones that isolatethe tape traffic from the DASD traffic and allo

Seite 113

Emulation topologyFICON device emulation topologies have unique requirements due to the characteristics of theemulation devices. Each device must trac

Seite 114 - Port-based address binding

connections that make emulation isolation difficult. By using Enhanced TI Zoning to support devicemembership in multiple zones, these types of emulati

Seite 115

Monitoring and Alerting Policy SuiteThe Monitoring and Alerting Policy Suite (MAPS) is an optional storage area network (SAN) healthmonitor supported

Seite 116

Brocade resourcesVisit the Brocade website to locate related documentation for your product and additional Brocaderesources.You can download additiona

Seite 117

Settings for FICON environmentsFor typical FICON environments, port fencing is usually only set for CRC errors and Invalid Words.The default of 1,000

Seite 118 - Unbinding multiple ports

Registered listenersTo display registered listeners for link incidents, connect to the switch, log in as user, and enter one ofthe following commands:

Seite 119

*IRD000E 1065,002032-001 LEVEL=1 FRU(S)=SLOT8 IOS000I 1065,AB,EQC,**,8200,,,*MASTER*, 286

Seite 120 - 53-1003144-01

Swapping port area IDsIf a port malfunctions, or if you want to connect to different devices without having to rewire yourinfrastructure, you can move

Seite 121 - EBCDIC Code Page

• Undetermined board types cannot be swapped. For example, a blade swap will fail if the bladetype cannot be identified.• Blade swapping is not suppor

Seite 122

Symptom Probable cause and recommended actionPackets are being dropped between two FICON units. Distance between devices is impacting data.When planni

Seite 123

Symptom Probable cause and recommended actionChannel path with two-byte addressing does not comeonline.The fabric may not be configured properly, cabl

Seite 124 - OxFE and OxFF ports

Symptom Probable cause and recommended actionSWITCH DEVICE NUMBER = NONEATTACHED ND = NOT KNOWNPHYSICAL CHANNEL ID = 01F0************************ SYMB

Seite 125 - SCC policy

you get confirmation that the configuration has been updated, ouput from the following will becollected and display for the supportShow command:‐ fico

Seite 126

Cascaded topology checklistVerify the following in your FICON environment to ensure proper functionality of the feature:• Fabric OS v6.1.0 or later is